KSO 202V and KSO 202VM Single-end service assembled chambers.

Designation

KSO chamber is designed to receive and distribute electric power in electrical facilities with three-phase 50 or 60 Hz alternating current, 6 or 10 kV voltages and with insulated neutral or neutral with Peterson-coil.

KSO switchgears are made to fulfill economic needs of the country and can be used as switchgears (including modular-building installment) with 6-10 kV voltage. KSO Switchgears are designed to receive and distribute electric power in industry, agriculture, electrical stations and substations of railroad transport.

Operational principal is defined by arrangements of main and auxiliary circuitries.

KSO switchgears can be used as high voltage devices for complex transformer substations of KTP-10/0,4 (-10/0,4) and BKTP-10/0,4 (-10/0,4) series with power from 100 to 2500 kVA.

Climatic versions are Y(moderate) and area class is 3 according to GOST 15150-69.

KSO 202V

Naming conventions

KSO-202V-<A>-<B> <C>

- chamber

S - assembled

- single-end service

202 - Type and year of development

V - distinguishing index of CHEAZ-ELPRY Ltd manufacturer.

<A> - Index of main-circuit arrangement

<B> - rated current

<C> - Climatic versions and area class according to GOST 15150 and GOST 15543.1


Example of naming for KSO-202V with 630 A rated current, main circuit arrangement N 8VV and climatic version Y3:

Switchgear KSO 202V-08VV-630 Y3 BKGI.674791.005TY


KSO-202VM-<A>-<B> <C>

- chamber

S - assembled

- single-end service

202 - Type and year of development

V - distinguishing index of CHEAZ-ELPRY Ltd manufacturer.

- compact version

<A> - Index of main-circuit arrangement

<B> - rated current

<C> - Climatic versions and area class according to GOST 15150 and GOST 15543.1


Example of naming for KSO-202VM with 630 A rated current, main circuit arrangement N 8VV and climatic version Y3:

Switchgear KSO 202VM-08VV-630 Y3 BKGI.674791.005TY

Special traits

  • compactness (front width - 750 mm, depth - 1100 mm);
  • switchgear is divided into several panels: high-voltage, relay and cable;
  • different kinds of interlocks for protection from wrong operations during maintenance and repair;
  • Convenient and simple maintenance;
  • full range of main circuit arrangement and secondary commutation circuit arrangement to fulfill all kinds of customers needs;
  • At customer request Russian and foreign commutation devices and relaying and automation devices (including microprocessor-based) can be used;
  • Replacement and connection without additional adaptation with KSO switchgears from next series: 2YM, 272, 285, 292, 298, 2000 etc.;
  • using modern techniques in manufacturing (metal cutting, bending and perforation on FINN-POWER automatic complexes, painting with powder paint);

General quantities of KSO-307

name of the parameter value
KSO-202V KSO-202V

Rated line voltage, kV

6; 10

Rated normal voltage (line), kV

7,2; 12

Rated current of main circuits, A

630; 1000; 1600

630; 1000

Rated breaking current, kA

12,5; 20

Thermal short-time current rating (3 seconds duration), A

20

Short-time withstand current, kA

51

Rated current of current transformers,

50; 75; 100; 150; 200; 300; 400; 600; 800; 1000; 1500

50; 75; 100; 150; 200; 300; 400; 600; 800; 1000

Rated current of busbar,

630; 1000; 1600

630; 1000

Rated current of busbar bridge, A

630; 1000; 1600

630; 1000

Rated power of auxiliary transformers installed in KSO switchgears, kVA

1,25; 25;40

1,25; 25;40

Rated voltage of supply circuits, V:
- protection, control and indication circuits with direct and alternating current
- Circuits of voltage transformers, V
- Circuits of auxiliary supplies transformers, V Lighting circuits:
- inside KSO chamber
- outside KSO chamber

 


220

100

220; 380

 

12

12; 220

 


220

100

220; 380

 

12

12; 220

Conventional fusing current,

3,2; 5; 8; 10; 16; 20; 31,5 ÷ 160

Note - thermal and withstand current ratings of current transformers are defined by their technical specification.


Rated values of climatic version are accorded with GOST 15150-69 and GOST 15543.1-89.

At that:

- environment temperature: from -45 up to +40º, for switchgear with breaker from -25 to +40 º;

- altitude: up to 1000m.

The environment is not explosive, not containing conductive dust, corrosive gases and vapors in high concentrations, which destroying metal and insulation (environment class is II according to GOST 15150-69).

Technical characteristics of installed devices

Used devices

Rated current, A

Rated breaking current, kA

Short-time withstand current, kA

Thermal short-time current, kA

Voltage, V

electromag. making current, A

electromag. breaking current, A

Operation time

/TEL-10-20/_2

1600

12,5

20

51

20

~220

=220

5

10

5

10

100000

/TEL-10-20/_2

1000

12,5

20

51

20

~220

=220

5

10

5

10

100000

Shell-10-31,5/_2

2000

20

31,5

51

80

20

31,5

~110/220

=110/220

5

10

5

10

30000

-

10-20/_2

630

1000

20

51

20

~220

=110/220

16

1,5

50000

-10

electromagnetic operator

1600

20

51

20

~220

=220

=110

35 (70)

-

50000

-10

spring drive

1600

20

51

20

~220

=220

=110

6; 3

3

2-

-

50000

-10-20/_2

1000

16(20) 31,5

51

80

20

31,5

~220

=220

=110

35

35

70

2,0

3,0

1,5

25000

--10-31,5/_2

1600

20

31,5

51

80

20

31,5

~110/220

=110/220

30 (90)

1,0 (2,0)

50000

--10-20/_2

630

1000

20

51

20

=110/220

~120/230

5

10

5

10

50000

Evolis

630

1250

25

31,5

62,5

80

25

31,5

~24/30

=48/60

110/130

220/250

-

0,6

 

3

25000

LF1

630

1250

25

31,5

64

81

25

31,5

~48/110/220

=24/30/110/

220

1,7

1,7

 

1

0,3

 

50000

Siemens

3-5

800

1250

32,8

40

-

-

~220

=220

2,5

2,5

2,5

2,5

10000

VD4

630

1250

16; 20 25; 31,5

40, 50, 63, 80

16; 20 25; 31,5

=110/220

~127/220

1,7

1,7

1

0,3

30000

-10-4/_2, 5

400

4

-

-

~220

=220

=110

5

5

10

5

5

10

750000

10-20

630

0,63

51

20

-

-

-

2000

-1-10/_-20

630

0,63

51

20

=110/220

~127/220

~380

10

10

2000

()-10-31,5/

Up to 1600

20

31,5

51

80

20

31,5

=110/220

~127/220

16/24/42

14/17/20

30000


 

Design

KSO switchgear is metal devices assembled from zinced metal sheets.

Devices of main circuits are placed inside the chamber. Hands of drive and control devices are placed on face side of the KSO switchgear. Relays of protection, control, indication as well as meter and measure devices are installed inside the chamber and on the face side of switchgear.

Access inside the KSO-202V switchgear is provided by means of two doors: upper to the section of high voltage breaker, voltage transformer or fuse; bottom to the section of cable connections, power transformer or disconnector. Between two section there is a removable barrier, which block the access to high voltage section. KSO chamber has windows to observe inside of the chamber.

Busbar bridges of KSO switchgear have net fencing or fencing with viewports on the front. All devices installed inside switchgear that have to be grounded are grounded.

Inside the chamber with cable entry there is an opportunity to use four 3-phase cable with a section up to 240 mm2 or 1-phase plastic-insulated cable with a section up to 500 mm2.

A box placed in the middle of the switchgear are used as a canal for main cables of disconnectors electromagnet and circuits of control and indication.

Additionally there is a terminal block inside the box for between section connections of auxiliary circuits.

To protect from wrong operation during maintenance or repair there are several interlocks in switchgears:

1. mechanical:

  •  interlock to protect from turning on or off linear and bus desconnectors while high voltage breaker is still on;
  •  An interlock to prevent turning on groundings blades if working blades of disconnector are on;
  •  An interlock to prevent turning on disconnector if groundings blades are on;

2. electrical:

  •  Interlock that prevent turning on the high voltage breaker if disconnector is in intermediate position;
  •  Interlock that prevent turning on feeders breaker and section breaker if groundings blades of busbar grounding is on.

By special request for other kinds of protection according to main circuit arrangement additional locks and control contact of grounding disconnector can be installed.

In double-row arrangement of KSO chamber busbar bridges are installed. Busbar bridge is a metal construction made from two frame with insulators, busbars and busbar holdings.