Site map
VCHRP-TM an universal VFD for AC industrial loads up to 17,500 kVA with 3 kV, 6 kV and 10 kV nominal output voltage. Due to high quality of development and production, VCHRP-TM can operate with the already installed and the new asynchronous or synchro- nous motors.
Ordering products

+7 (8352) 39-57-41, 39-50-88, 39-50-85, 55-52-65

fax +7(8352) 62-38-74

secret@elpri.ru
 " - ".
Single-end service assembled chamber of KSO 306 and KSO 306 SHVV series.

Designation.

KSO 306 single-end service assembled chamber is designed to receive and distribute electric power in electrical facilities with three-phase 50 or 60 Hz alternating current, 6 or 10 kV voltages and with insulated neutral or neutral with Peterson-coil.

KSO-306 SHVV is designed for high-voltage feeder for different facilities with 6 or 10 kV voltage.

Climatic versions are Y(moderate) or T(warm), and area class is 3 according to GOST 15150. Rated values of climatic factors are accorded to GOST 15150 and GOST 15543.1.

  • Ambient temperature: -45 C to +40 C
  • Altitude: up to 1000m.
  • Level 9 of MSK Earthquake Scale
  • The environment is not explosive, not containing conductive dust, corrosive gases and vapors in concentrations enough to destroy metal.
KSO 306 single-end service assembled chamber

Naming conventions for KSO 306 and KSO 306 SHVV type switchgear

KSO-306 -- Chamber
KSO-306 -- Assembled
KSO-306 -- Single-end service
KSO-306 -- Type and year of development
KSO-306 -- SHVV high-voltage entrance cabinet (for KSO 306 SHVV series)
KSO-306 -- Name for main-circuit arrangement
KSO-306 -- Rated current
KSO-306 -- Rated voltage:
06 6 kV, 10 - 10 kV
KSO-306 -- Climate-specific design and area class according to GOST 15150
and GOST 15541.2 classification.

Examples:

1) KSO-306 switchgear with 630 A rated current, 10 kV rated voltage, number 4 main-circuit arrangement and climatic version Y3:
KSO-306-04-630 10 Y3 BKGI.674731.040 TU

2) High-voltage entrance cabinet KSO-306 SHVV with 630 A rated current, 10 kV rated voltage, number 01 main-circuit arrangement and climatic version Y3:
KSO-306 SHVV 01- 630 SHVV 10 Y3 BKGI.674731.040 TU.

General quantities and technical data


KSO-306 KSO-306 SHVV
Rated line voltage, kV 6; 10 6; 10
Rated normal voltage (line), kV 7,2; 12 7,2; 12
Main circuit rated current, A 400; 630 400; 630
Rated breaking current, A 630 630
Thermal short-time current rating (3 seconds duration), A 20 20
Short-time withstand current, 51 51
Rated current of current transformer, 50; 75; 100; 150; 200; 300; 400; 600 -
Rated current of busbar, 630 -
Rated current of busbar bridge, A 630 -
Rated voltage of support circuitry, V 220;380 220;380
Light circuitry in KSO panel, V 36; 220 36; 220
Conventional fusing current, 2; 3,2; 5; 8; 10; 16; 20; 31,5 + 160;200
Insulation level as to GOST 1516.1 With normal insulation
Existence of insulation of main circuit bus bar Without insulation
System of busbar With one set of busbar
Types of linear high-voltage feeders (bonds) cable and bus connection
Protection class as to GOST 14254 IP20 for front and side panels
IP30 - for side walls of outward panels;
IP00 for other parts of KSO

Components

Depending on build-in equipment KSO can be divided into several types:

  • KSO cabinet with load-breaker VNA (); VNP-M1 (-1);
  • KSO cabinet with load-breakers and fuses;
  • KSO cabinet with voltage transformers NOM(), NAMI(), NAMIT(), NTMI(), NOL.08(.08) and with antiresonance group 3ZNOL.06(3.06), 3ZNOLP.06(3.06);
  • KSO cabinet with load-breakers and fuses;
  • KSO cabinet with isolating switch RVZ for 630 A and PR-10 (-10) leverage;
  • KSO cabinet with surge protector;

Design

All mechanisms, current conducting parts, insulating devices, mounts and supporting frames are designed in a way to protect maintenance staff and insulation in KSO chamber from ejected gas and oil. KSO chamber has front window to control position of switching devices.

Inside all chambers there is a receptacle for light bulb with opportunity to safely change the light bulb without turning off power in main or supplementary circuits. There are also sockets for mobile lamps and switch for inside lighting on the front door.

Doors can be locked with keys.

There are several protection interlocks in KSO chamber:

  • An interlock to prevent doors opening while load-breaker is on;
  • An interlock to prevent doors opening while grounding blades are disconnected;
  • An interlock to prevent turning on grounding blades if working blades of isolating switches or load-breakers are on;
  • An interlock to prevent turning on isolating switches if grounding blades are on;

For other kind of protection according to main circuit arrangement additional locks and circuit breaker detectors can be installed for special request.

KSO-306 chambers can be connected with other chambers of KSO 300 series by using connecting panels.

Connection of busbar of two KSO chambers placed in front of each other (fig. 2.4, 2.5) can be done by busbar bridge or cable bridge. Busbar bridge is produced for special request. Length of cable bridge is made for 2000 mm, 2500 mm or 3000 mm distance between two chambers.

Bus bridges are manufactured with or without isolating switch. Leverage of isolating switch is placed on special panels (fig. 2.5).

Overall dimensions, main-circuit arrangements are described below:

Fig. 2.1. Overall, installation and linkage dimensions of KSO-306 (-306) with hard-gas load-breaker VNA-10/630 (-10/630).  
) I variant of KSO-306 SHVV installation;
) II variant of KSO-306 installation;

Overall, installation and linkage dimensions of KSO-306 (-306) with hard-gas load-breaker VNA-10/630 (-10/630)

Fig. 2.2. Overall, installation and linkage dimensions of KSO-306 (-306) with hard-gas load-breaker VNP-M1-10/630 (-1-10/630).

Overall, installation and linkage dimensions of KSO-306 (-306) with hard-gas load-breaker VNP-M1-10/630 (-1-10/630).

Fig. 2.3. KSO-306 SHVV (-306 ) overall, installation and linkage dimensions.
) I variant of KSO-306 SHVV;
) II variant of KSO-306 SHVV;

, ,   -306

Fig. 2.4. Overall, installation and linkage dimensions of KSO-306 SHVV (-306 ) with bus connection.

1,2 - frame; 3 insulator; 4,5,6,7 - bus; 8,9 - panel.

Overall, installation and linkage dimensions of KSO-306 SHVV (-306 ) with bus connection.

Fig. 2.5. Overall, installation and linkage dimensions of KSO-306 (-306) with insulation switch installed on bus connection.

1,2 - frame; 3 insulator; 4 - bus; 5 - insulation switch; 6,7,8 - bus; 9,10 - haulage; 11,12 - panels.

Overall, installation and linkage dimensions of KSO-306 (-306) with insulation switch installed on bus connection.

Elements naming on single-line scheme:
QW load-breaker;
Qs1 isolating switch RVZ-10 (-10);
QSC1 grounding blades of RVZ-10 (-10) isolating switch;
QSC2 grounding blades of load-breaker;
-TA2 current transformers TOL-10 (-10);
TVTV voltage transformer NOM(), NAMI(), NAMIT(), NTMI(), NOL.08(.08) and with antiresonance group 3ZNOL.06(3.06);
FUFU fuses of PKT(E)-10(6) type (()-10(6));
FV surge protector.

KSO-306 main-circuit arrangement

KSO-306 main-circuit arrangement