Site map
VCHRP-TM Ц an universal VFD for AC industrial loads up to 17,500 kVA with 3 kV, 6 kV and 10 kV nominal output voltage. Due to high quality of development and production, VCHRP-TM can operate with the already installed and the new asynchronous or synchro- nous motors.
Ordering products

+7 (8352) 39-57-41, 39-50-88, 39-50-85, 55-52-65

fax +7(8352) 62-38-74

secret@elpri.ru
ќќќ "„Ёј« - ЁЋѕ–»". ѕередовые технологии в разработке и производстве энергосберегающего оборудовани€
Frequency converters EPV-VL

EPV-VL converters is designed to control induction or synchronous motor of power range from 0.25 to 30 kW and have small dimensions. You can choose optimum electric drive for all operating conditions due to the compact mounting, various protection and EMC class. Electric drive EPV-VL is the best solution if small dimension and various types of mounting (by the rear or lateral part) are needed. VL converters are easy to use. EPV-VL has an integrated RS485 (Modbus) socket. You can install in the frequency converter an optional I / O boards and interface expansion board in addition to the standard of I/O.

Advantages

  • Speed accuracy in the steady state <1%

  • Low torque ripple

  • High immunity to resonance vibrations

  • Starting torque> 200%, depending on the engine power of the electric motor and frequency converter

  • Can be used in multi-motor drive

 

Multi-purpose macro program - for standard solutions

Easy in use and flexible multi-purpose macro program is included as a standard in the electric drive EPV-VL. The probability that it will require an additional configuration is very low. All inputs and outputs - freely programmable. Variety of functions are included, for example, electric motor protection, flying start, sleep-wake, PID control with the ability to control a group of 3 pumps.

Electric drive EPV-VL 380-500 V, IP21, EMC H, hinged version module

TYPE of
FREQUENCY
CONVERTER
 

Electric motor shaft power and current

FR/IP

DIMENSIONS
W x H x D
mm/span>
 

WEIGHT
,kg
 

Overload
150 %
Overload
110%

P, kW

I(V), ј

P, kW

I(H), ј

EPV-VL00035C2H1SSS

0,75

2,2

1,1

3,3

MF4/IP21

128x292x190

5

EPV-VL00045C2H1SSS

1,1

3,3

1,5

4,3

MF4/IP21

128x292x190

5

EPV-VL00055C2H1SSS

1,5

4,3

2,2

5,

MF4/IP21

128x292x190

5

EPV-VL00075C2H1SSS

2,2

5,6

3

7,6

MF4/IP21

128x292x190

5

EPV-VL00095C2H1SSS

3

7,6

4

9

MF4/IP21

128x292x190

5

EPV-VL 00125C2H1SSS

4

9

5,5

12

MF4/IP21

128x292x190

5

EPV-VL00165C2H1SSS

5,5

12

7,5

16

MF5/IP21

144x391x214

8,1

EPV-VL00235C2H1SSS

7,5

16

11

23

MF5/IP21

144x391x214

8,1

EPV-VL00315C2H1SSS

11

23

15

31

MF5/IP21

144x391x214

8,1

EPV-VL00385C2H1SSS

15

31

18,5

38

MF6/IP21

195x519x237

18,5

EPV-VL00465C2H1SSS

18,5

38

22

46

MF6/IP21

195x519x237

18,5

EPV-VL00615C2H1SSS

22

46

30

61

MF6/IP21

195x519x237

18,5

Unit designation of the electric drive

EPV-VL 0007 5 C 2 H 1 SSS OO AI
1 2 3 4 5 6 7 8 9 10

1 Ц The vector control elecdric drive EPV-VL
2 Ц Rated current
3 Ц Power supply voltage: 2 Ц 208Е240 V; 5 Ц 380Е500 V
4 Ц Control Panel: C - keyboard with 7-segment LCD display; B - without panel
5 Ц Protection class: 2 Ц IP21; 5 Ц IP54
6 Ц The level of interferences emission: Ќ Ц meets the standard EN 61800-3 (2004), category C2; — Ц meets the standard EN 61800-3 (2004), category —1; “ Ц low earth fault current for IT lines
7 Ц Brake chopper: 1 Ц internal brake chopper (standard)
8 Ц Modification of the device (power module, special designs, coating of the boards): SSS - standard; SSV Ц varnished board; STS - flange mounting
9 Ц Mounted (on the factory) fieldbus boards (socket D): 00 Ц not mounted; —3 Ц Profibus DP
10 Ц Mounted (on the factory) I/O expansion boards (socket ≈): 00 Ц not mounted; AI Ц I/O expansion board (3xDI, 1xRO, 1xThermistor); јј Ц I/O expansion board (3xDI, 1xRO, 1xDO); —3 Ц Profibus DP